THE HYBRID TELECOM SOLUTION WITH LITHIUM BATTERY

MAIN FEATURES

  • Lower CO2 emissions
  • Lower fuel consumption
  • No acoustic pollution (in battery mode)
  • Extended maintenance interval
ENERMAX-CUMMINS

GENERATING SET

Unit

Model

KL18HP DC48

Output Power (max)kW15,5
VoltageV48 DC
Control PanelAUS 7310
Fuel Tankl860
Fuel Consumption 70% loadl/h1,2*
Weightkg1350
Dimensions (LxWxH)mm2274x1034x2000
* Consumption figures are in liters per hours of 3 kW average load supplied
ENERMAX-CUMMINS

ENGINE

Unit

KOHLER

Model

KDW1404

SpeedVariable
Revolutionsrpm1200-2800
kWm MaxkWm17,9 @ 2700 rpm
RegulatorElectronic
Cylinder and arrangement4 L
Total displacementcm³1372
AspirationNatural
Emissions compliance

STAGE V

ENERMAX-CUMMINSloghi

GENERATOR

Unit

Model

PMG-DC2700 185 PF

Technology

permanent magnet
VoltageV48 DC
CurrentA267
Max output powerkW15,5
Pole20
ENERMAX-CUMMINS

LITHIUM BATTERY

Unit

BATTERY OPTION

Battery VoltageV DC48V DC
Model

PJ048 -111 RK1

Brand

Manufacturing CountryItaly
Lithium cell chemistryLiNMC
Quantityn3
Nominal capacityAh3 x 111 = 333
Nominal energykWh16
Weightkg3 x 58 = 174
Charging timeh1 h : 18 min
Round trip efficiency%>98
Life cycle>5000 cycles - @ 80% DOD

POWER GENERATOR’S EQUIPMENT

  • Galvanized steel soundproofed canopy
  • Fully bunded fuel tank
  • Forklift guides
  • Manual oil extraction pump
  • 12V engine starter battery
  • 48V battery isolator switch
  • Noise level: 68 dB(A)@7m
  • Option: lifting eye
  • Option: air conditioned
  • Option: solar charger for photovoltaic system
  • Option: automatic fuel refilling kit
  • Option: 12V battery isolator switch

FULL CUSTOMIZATION AVAILABLE FOR BATTERY AUTONOMY, GEN SET POWER AND COUPLED PHOTOVOLTAIC FIELD